PLC-based PACs fill the gap between traditional distributed control systems and basic programmable logic controllers.

Because of the complicated nature of pump flow and pressure control, industrial plants have often incorporated control of complex pumping and related systems using distributed control systems (DCSs) or expensive specialized controllers. In the past, many programmable logic controllers (PLCs) were not up to the task, so engineers and designers turned to DCSs or similar controllers, which, in some cases, can lead to higher costs and complex implementation.

Today, new alternatives allow monitoring and control of these complex systems with programmable automation controllers (PACs), saving considerable expense and simplifying implementation.

The PAC, or PLC-based PAC, fills the gap between the DCS and basic PLC. It has the hardware and software required to monitor, control and communicate with these pumping systems (see Figure 1, page 32).

Advanced Process Control

Complex pumping systems often require advanced process control (APC), which goes beyond proportional-integral-derivative (PID) control and can include methods such as model predictive control, inferential control and sequential control.

PID is sometimes insufficient because the process that needs to be controlled has a long dead time, is non-linear or presents other difficulties.

Various APC control methods and algorithms are supported in DCS platforms but not in most PLCs. PLC-based PACs, on the other hand, can execute many APC algorithms and typically have some built-in APC capability.

Some APC methods require complex custom coding, a programming technique supported by DCS platforms but not by most PLCs. The PLC-based PAC solves this problem because it allows users to create custom code, encapsulate it and integrate it into the overall controller program.

When APC is required, a PLC-based PAC provides many of the capabilities of a DCS but at a lower cost and with simpler implementation. Pushing a basic PLC to perform APC is impossible in some cases, and even high-end PLCs can require an extraordinary amount of effort to implement APC.

Interfacing to Instruments

Pumping systems for applications such as custody transfer often contain a large number of instruments and analyzers. Typical instrument types include flow, pressure, temperature and density. Many of these instruments are multivariable, measuring several parameters at once. Modern pumping systems often employ smart instruments with a built-in, two-way digital data link, rather than simple instruments with a 4- to 20-milliamps (mA) output proportional to the measured variable.

For example, custody transfer applications often use mass flow meters because they can precisely measure the amount of liquids transferred from one owner to the next regardless of product density. Coriolis meters measure multiple variables including flow, density and temperature and are most commonly used to measure mass flow.

These variables are sent to the control system along with diagnostic, calibration and other information. A typical Coriolis meter used in custody transfer will transmit hundreds of parameters to the control system over a digital data link, presenting data storage and handling challenges.

Plants often employ analyzers to measure parameters related to the chemical composition of oil and other liquid hydrocarbons. Like smart instruments, analyzers are usually connected to the control system via a two-way digital data link and often transmit more than a hundred parameters to the control system.

Complex pumping systems commonly employ smart valves. Like smart instruments and analyzers, smart valves communicate large amounts of data with the control system over two-way digital data links.

A DCS will have built-in communication capabilities for a number of the process control protocols used by smart instruments, smart valves and analyzers. While a PLC will have more limited communications capabilities, a PLC-based PAC will have an extensive array of built-in communication ports and protocols, with the ability to expand through plug-in communication modules.

Data Handling

Image 1. Each of these smart Coriolis mass flow meters provides hundreds of parameters of information related to measurement, diagnostics and calibration. A PLC-based PAC is well-suited to interface with these instruments and to handle the large volumes of data they produce. (Images courtesy of AutomationDirect.com)Image 1. Each of these smart Coriolis mass flow meters provides hundreds of parameters of information related to measurement, diagnostics and calibration. A PLC-based PAC is well-suited to interface with these instruments and to handle the large volumes of data they produce. (Images courtesy of AutomationDirect.com)

Smart instruments, smart valves and analyzers produce large amounts of data (see Image 1). A DCS can handle the storage and processing of this data, but a PLC generally cannot. A PLC-based PAC provides the needed data capabilities at a lower cost and with simpler implementation than a DCS.

With integrated mass storage devices such as removable USB drives and microSD cards, PLC-based PACs can manage large amounts of data locally in the controller. Custom utilities in the programming software allow data logging on the memory device and configuration of the trigger for rate-of-data storage. Data is stored in a comma-separated variable file format, making it simple to read and manipulate the information.

Most PLC-based PACs have the option to remove the memory device from the controller and then download files directly to a PC or laptop. Built-in Web server functionality allows access to this data from almost anywhere using any standard Web browser. Users just need to type in the Internet Protocol (IP) address of the PLC-based PAC, and with the proper connectivity provisions and security considerations, they have instant access to the data files.

Image 2. A PLC-based PAC has the capability to accommodate thousands of I/O points of many different types, a feature often required for control and monitoring of complex pumping systems.Image 2. A PLC-based PAC has the capability to accommodate thousands of I/O points of many different types, a feature often required for control and monitoring of complex pumping systems.

Lots of I/O

Refineries and power plants often have thousands of input/output (I/O) points, many of which are analog and related to the control and monitoring of pumps and related systems. A PLC-based PAC can handle many I/O points, even when the majority of them are analog (see Image 2). The available memory in a PLC-based PAC is more comparable to a DCS than a typical PLC. It will easily support thousands of I/O points and have the program space necessary to handle these more complex applications.

Another benefit of a PLC-based PAC is the tag-based control environment, which gives the flexibility to assign data types—and by extension, memory allocation—as needed. Most PLCs have a fixed-memory map, leaving the PLC designer with no flexibility regarding the right balance of memory allocation for the application.

Image 3. Custody transfer and other pump skids often contain high-precision instrumentation. The information from these instruments must be collected, stored and sent to higher level computing systems.Image 3. Custody transfer and other pump skids often contain high-precision instrumentation. The information from these instruments must be collected, stored and sent to higher level computing systems.

Higher Level Computing System Communication

Control systems for these types of applications often require communication to higher level computing systems. A custody transfer skid, for example, may be controlled by a PLC-based PAC, but it must communicate to a plant-wide DCS. The control system in a refinery or power plant is often tied to an enterprise resource planning system.

Getting data to the people who need it has never been an easy task for a PLC, but a PLC-based PAC takes much of the work out of this process. Reporting data to higher level systems often requires interface with Structured Query Language, Access or other Open Database Connectivity database applications. The tag database of the PLC-based PAC is easily shared with bridge applications, allowing manipulation of the database via standard actions such as insert, delete, update or select.

Conclusion

A DCS has been the platform of choice for control and monitoring of complex processes, many of which contain large numbers of pumps. While the DCS is quite capable, it can be expensive and difficult to implement. PLCs are less expensive and easier to apply but often are not capable of the task. The PLC-based PAC, however, was created to fill the gap between a DCS and a PLC and can be ideal for these types of applications.

Figure 1. PLC-based PAC capabilities for complex control

  • APC
  • Structure text language for complex functions and calculations
  • Sequential function charts for process control
  • Integration with smart instruments, smart analyzers and valves
  • Can store large amounts of data
  • Advanced data handling
  • Can handle thousands of analog I/O points
  • Easy to integrate with higher level computing systems